MAX series boilers

Ekopell Max

Zobacz produkt w 360°
Discontinued equipment

Advantages of boiler:

  • design of boiler with fuel feeding system protected by the patent Pat. 224952,
  • made of the high-quality certified steel sheets. Intended for combustion of pellet with a 6-8 mm diameter.
  • combustion process and control of equipment operation is performed through the electronic controller,
  • safety temperature limited in case of increase in temperature in the boiler, above 95oC,
  • equipped with automatic blowing igniter,
  • the furnace is equipped with retort burner, where all combustion processes with air supplied by the blowing fans with division into primary and secondary air, takes place,
  • radiator plate installed above the burner, afterburning the flammable gases and distributing uniformly flue gas to the heat exchanger,
  • the body consists of, among others, crosswise water tubes ensuring reception of considerable amount of heat just behind the burner and the convection part, where two-draught horizontal smoke tube heat exchanger changes into the flue,
  • arrangement of the inspection doors facilitates operation and maintenance operations,
  • the rotary feeder used protects against flashback towards the container,
  • automatic water “FIRE FIGHTER II” fire suppression system - protection against flashback to fuel feeder system.

 

Trouble-free operation of the EKOPELL MAX boiler is ensured by the use of the pellet with adequate quality and grain size. It is forbidden to use substitute fuel in form of: kernels, shells, grains. The boiler-room should meet the applicable requirements given in the Regulation of the Minister of Infrastructure and by in compliance with the provisions and conditions included in the Polish Standard. MAX series boilers require special attention if there is no electrical power, mainly due to stoppage of pumps operation and other control automation *.

* The user’s manual is an integral part of the product. You should read carefully guidelines and hints related to assembly and operation. The boiler should be assembled by qualified personnel acc. to the recommendations of the applicable standards and guidelines of the manufacturer.

 

 

 

 

4 lata 4 years of warranty for heat exchanger tightness, 2 years for the remaining components and efficient operation of the boiler.
stal Heat exchanger made of certified high-grade steel.
sprawnosc_90+915.jpg High energy efficiency from 90.0% to 91.5% thanks to increased heat recovery from flue gases.
kipr_max.jpg
Servicing four pumps (central heating, domestic hot water, 1 pump - additional output.) PID function. Weekly operation programme and weather compensated control. ON-LINE change and a preview of parameters of the main controller through installed internet module with RJ-45 socket; Possibility to connect room controller - extra paid option. Possibility to connect two mixing valves using the modules (I-1, I-1M).
 system_automatycznego_czyszczenia.jpg Pneumatic cleaning system for heat exchanger - extra paid option.
dtr.jpg Boiler adapted for operation in the central heating system in the open and closed system provided the protections have been installed in accordance with the operation and installation manual of the boiler.
Retort burner - solution protected by the patent Pat. 224952.
Radiator plate afterburning the flammable gases and distributing uniformly heat in the combustion chamber.
 powietrze.jpg Controlled distribution of primary and secondary air.
 system_gaszenia.jpg “FIRE FIGHTER II” - an automatic system intended for fire suppression with water from the water supply system, intended as a protection against flashback to fuel feeder system.
uchwyt.jpg It is equipped with handles facilitating loading with a hoist.
opcje.jpg It is possible to adapt the boiler with respect to technical properties and additional equipment to the requirements of the given project.

 

EKOPELL MAX 75 kW dimensions:

 

 

 

 

EKOPELL MAX 100 - 300 kW dimensions:

 

 


 

Boiler dimensions in mm
dimension
75 kW 100 kW 150 kW 200 kW 300 kW
A 784 1194 1194 1394 1624
B 1645 1098 1098 1148 1264
C 1680 3648 3648 3794 4149
D 1817 1758 1758 1729 1753
E 1492 2078 2078 2078 2551
F 1296 1885 1885 1885 2358
G 246 1501 1051 1451 1925
H 376 246 246 296 296
I 140 336 336 336 386
J 1046 440 440 440 272
K 1440 146 146 146 146
L 1960 1801 2001 2001 2001
M 127 117 145 148 139
N 965 2317 2517 2517 2583

O

912

1586

1786

1786

733

P

806

1495

1492

1687

1935

R - 599 599 699 814

S

-

1106

1106

1106

1106

T

-

1112

1112

1112

1112

 

TECHNICAL DATA

Specification / boiler type

unit 75 100 150 200 300

Heating area

m2

5,9 12 14 23,5 29

Area of heated rooms 1

m2

to 750 to 1000 to 1500 to 2000 to 3000

Capacity of fuel container 2

kg ~250 ~485 ~485 ~485 ~485

Fuel consumption 3

kg/h 15,9 21,5 32,7 42,0 66,7

Burn time

h ~16 ~23 ~15 ~12 ~7

Efficiency for nominal power

% 91,2 91,5 90,6 90,3 90,0

Efficiency for minimum power

% 90,0 89,1 89,3 89,4 90,7

Max. permissible work pressure

bar 2,5 2,0

Required flue gas draught

mbar 0,38 0,40 0,44 0,46 0,50

Max. water supply temperature

°C 65/80

Min. return water temperature

°C 55

Boiler weight

kg 1104 2651 2891 3306 4718

Container weight

kg ~139 ~204 ~204 ~204 ~204

Feeder weight

kg ~12 ~195 ~195 ~210 ~228

System weight (boiler, container, feeder)

kg ~1255 ~3050 ~3290 ~3720 ~5150

Boiler water tank capacity

l 355 790 890 1350 1600

Chimney section

cmxcm 25x25 27x27 32x32 37x37 45x45

Chimney section

Ø mm

280 305 365 415 505

Minimum chimney height 

m

11

12,5

14

14,5

15,5

Diameter of supply and return 

cal

3’’

Release socket diameter

cal

1”

Flue size

mm 246 246 246 296 296

Power supply

V/Hz/A

~230/50/0,9

~400/50/0,9

Power consumption

W

1200 / 820

2060 / 1600

2060 / 1600

2060 / 1600

2060 / 1600

Noise level

dB

<75

 

1 Maximum heated area has been calculated based on individual demand for heat q=100 W/m2.

2 Charging density of pellet 0,6 kg/dm3.

3 Fuel consumption for pellet with calorific value17 000±300 kJ/kg.

 